Power-Cycling Controllers
The GenFlow controller has a battery backup that it automatically switches to in the event of mains power being disconnected.
Intentionally causing this disconnection can be helpful when restarting a faulty controller, but disconnecting the controller from the mains entirely may be difficult or time-consuming in a live environment.
How to quickly power-cycle a controller without disconnecting the mains:
- Open the controller and locate the IEC power supply.
- Disconnect the green two-pin connector with the red and red/black wires from the 6 pin socket at top of the power supply. (picture below)
- Reconnect the green two-pin connector in the same place.
The SOLID RED wire MUST ALIGN with the 12V PIN on the 6 pin socket.
The BLACK/RED wire MUST ALIGN with the 0V PIN on the 6 pin socket.